Decentral Solutions
(LOC+DIG CTRL/AS P100)
[4]
Function:
This is where the required function is selected if,
in parameter 002
Local/remote operation, Local
operation
[1] has been chosen.
Description of choice:
If
Local not active
[0] is selected, it is not possible to
set a reference via parameter 003
Local reference
.
In order to enable a shift to
Local not active
[0],
parameter 002
Local/remote operation
must be
set to
Remote operation
[0].
Local control and open loop
[1] is used if the motor
speed is to be set via parameter 003
Local reference
.
When this choice is made, parameter 100
Configuration
automatically shifts to
Speed regulation, open loop
[0].
Remote-operated control and open loop
[2] functions
in the same way as
Local control and open loop
[1]; however, the variable frequency drive can also
be controlled via the digital inputs.
Local control as parameter 100
[3] is used when the
motor speed is to be set via parameter 003
Local
reference
, but without parameter 100
Configuration
automatically shifting to
Speed regulation, open loop
[0].
Remote-operated control as parameter 100
[4]
works the same way as
Local control as parameter
100
[3]; however, the variable frequency drive can
also be controlled via the digital inputs.
Shifting from
Remote operation
to
Local operation
in parameter 002
Local/remote operation
, while this
parameter has been set to
Remote-operated control
and open loop
[1]: The present motor frequency and
direction of rotation will be maintained. If the present
direction of rotation does not respond to the reverse
signal (negative reference), the reference will be set to 0.
Shifting from
Local operation
to
Remote operation
in parameter 002
Local/remote control
, while
this parameter has been set to
Remote-operated
control and open loop
[1]: The configuration
selected in parameter 100
Configuration
will be
active. The shift will be smooth.
Shifting from
Remote control
to
Local control
in
parameter 002
Local/remote operation
, while this
parameter has been set to
Remote-operated control
as parameter 100
[4]: the present reference will
be maintained. If the reference signal is negative,
the local reference will be set to 0.
Shifting from
Local operation
to
Remote operation
in parameter 002
Local/remote operation
, while
this parameter has been set to
Remote operation
:
The local reference will be replaced by the
remote-operated reference signal.
014 Local stop
(LOCAL STOP)
Value:
Not active (DISABLE)
[0]
✭
Active (ENABLE)
[1]
Function:
In this parameter, the local [STOP]-key can be
engaged or disengaged on the control panel
and on the LCP control panel.
Description of choice:
If
Not active
[0] is selected in this parameter,
the [STOP]-key will be inactive.
NOTE
If
Not active
[0] is selected, the motor cannot
be stopped by means of the [STOP]-key.
015 Local jog
(LOCAL JOGGING)
Value:
✭
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the jog function on the LCP control
panel can be engaged/disengaged.
Description of choice:
If
Not active
[0] is selected in this parameter,
the [JOG]-key will be inactive.
016 Local reverse
(LOCAL REVERSE)
Value:
✭
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark