Decentral Solutions
Programming, FCD
300
Function:
You can choose between a linear, a sine-shaped
and a sine
2
-shaped ramp process.
Description of choice:
Select the required ramp type depending on
requirementsfor the acceleration/deceleration process.
207 Ramp-up time 1
(RAMP-UP TIME 1)
Value:
0.02 - 3600.00 sec
✭
3.00 sec
Function:
The ramp-up time is the acceleration time from 0
Hz to the rated motor frequency f
M,N
(parameter
104
Motor frequency, f
M,N
). It is assumed that the
output current will not reach the current limit (set
in parameter 221
Current limit I
LIM
).
Description of choice:
Set the required ramp-up time.
208 Ramp-down time 1
(RAMP DOWN TIME 1)
Value:
0.02 - 3600.00 sec
✭
3.00 sec
Function:
The ramp-down time is the deceleration time
from the rated motor frequency f
M,N
(parameter
104
Motor frequency, f
M,N
) to 0 Hz, provided
no overvoltage arises in the inverter because of
generating operation of the motor.
Description of choice:
Set the required ramp-down time.
209 Ramp-up time 2
(RAMP UP TIME 2)
Value:
0.02 - 3600.00 sec.
✭
3.00 sec
Function:
See description of parameter 207
Ramp-up time 1
.
Description of choice:
Set the required ramp-up time. Shift from ramp 1 to
ramp 2 by activating
Ramp 2
via a digital input.
210 Ramp-down time 2
(RAMP DOWN TIME 2)
Value:
0.02 - 3600.00 sec.
✭
3.00 sec
Function:
See description of parameter 208
Ramp-down time 1
.
Description of choice:
Set the required ramp-down time. Shift from ramp 1 to
ramp 2 by activating
Ramp 2
via a digital input.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port