Decentral Solutions
Out of the feedback range,
the feedback signal is out
of the programmed range in parameters 227 and 228.
Mechanical brake control,
enables you to control an
external mechanical brake (see section about control
of mechanical brake in the Design Guide).
Control word bit 11,
bit 11of the control word, the
relay output will be set/reset according to bit 11.
327 Pulse Max. 33
(PULSE MAX 33)
Value:
150 - 110000 Hz
✭
5000 Hz
Function:
This parameter is used for setting the signal value
that corresponds to the maximum value set in
parameter 205
Maximum reference, Ref
MAX
or to
the maximum feedback value set in parameter
415
Maximum feedback, FB
MAX
.
Description of choice:
Set the required pulse reference or pulse feedback
to be connected to terminal 33.
328 Pulse Max. 29
(PULSE MAX 29)
Value:
1000 - 110000 Hz
✭
5000 Hz
Function:
This parameter is used for setting the signal value
that corresponds to the maximum value set in
parameter 205
Maximum reference, Ref
MAX
or to
the maximum feedback value set in parameter
415
Maximum feedback, FB
MAX
.
Description of choice:
Set the required pulse reference or pulse feedback
to be connected to terminal 29.
341 Digital output terminal 46
(DO 46 FUNCTION)
Value:
✭
No function (NO OPERATION)
[0]
Value [0] - [20] see parameter 323
Pulse reference (PULSE REFERENCE)
[21]
Value [22] - [25] see parameter 323
Pulse feedback (PULSE FEEDBACK)
[26]
Output frequency (PULSE OUTPUTFREQ)
[27]
Pulse current (PULSE CURRENT)
[28]
Pulse power (PULSE POWER)
[29]
Pulse temperature (PULSE TEMP)
[30]
Control word bit 12 (CTRL. W. BIT 12)
[31]
Function:
The digital output can be used for giving the present
status or warning. The digital output (terminal 46) gives
a 24 V DC signal when a given condition is fulfilled.
Description of choice:
External Ref
MIN
- Ref
MAX
Par. 0-342.
An output signal is obtained, which is proportional
to the resulting reference value in the interval
Minimum reference, Ref
MIN
- Maximum reference,
Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
Par. 0-342.
An output signal is obtained, which is proportional to the
feedback value in the interval Minimum feedback, FB
MIN
- Maximum feedback, FB
MAX
(parameter 414/415).
0-f
MAX
Par. 0-342.
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
MAX
(parameter
202
Output frequency, high limit, f
MAX
).
0 - I
INV.
Par. 0-342.
An output signal is obtained, which is proportional
to the output current in the interval 0 - I
INV.
0 - P
M,N
Par. 0-342.
An output signal is obtained, which is proportional to
the present output power. Par. 342 corresponds to the
value set in parameter 102
Motor power, P
M,N
.
0 - Temp.
MAX
Par. 0-342.
An output signal is obtained, which is proportional to
the present heatsink temperature. 0 Hz corresponds
to a heatsink temperature of less than 68 °F (20 °C),
and 20 mA corresponds to 212 °F (100 °C).
✭
= factory setting. () = display text [] = value for use in communication via serial communication port