Decentral Solutions
4
20%
40%
60%
80%
Motor voltage %
Time, sec.
Start-stop Profile no: 14
100%
8
[DIP Switch settings
A1,A2,A3:ON; A4:OFF]
7 Sec.
5 Sec.
Start ramp
Stop ramp
2
6
Run
4
20%
40%
60%
80%
Motor voltage %
Time, sec.
Start-stop Profile no: 7
177ha025.10
100%
8
[DIP Switch settings
A1:OFF; A2,A3,A4:ON]
4 Sec.
Start ramp
Coast to stop
2
6
Run
■
Start/ stop profile setting table:
Start/stop
Profile
Start
Performance
Stop
Performance
1
(A1)
2 (A2)
3 (A3)
4
(A4)
Initial
Voltage
(%)
Start
Ramp
Time
(sec) #
Stop
Ramp
time
(sec) #
0
Equivalent to
DOL
Coast to stop
Off
Off
Off
Off
80
0.25
*
1
Fastest
Off
Off
Off
On
80
0.5
*
2
|
Off
Off
On
Off
60
0.75
*
3
|
Off
Off
On
On
60
1.5
*
4
|
Off
On
Off
Off
60
1.0
*
5
|
Off
On
Off
On
50
2
*
6
|
Off
On
On
Off
40
3
*
7
|
Off
On
On
On
50
4
*
8
|
On
Off
Off
Off
60
6
*
9
Slowest
Coast to stop
On
Off
Off
On
60
8
*
10
Fastest
Fastest
On
Off
On
Off
60
2
1
11
|
|
On
Off
On
On
50
3
2
12
|
|
On
On
Off
Off
40
4
3
13
|
|
On
On
Off
On
40
5
3
14
|
|
On
On
On
Off
30
7
5
15
Slowest
Slowest
On
On
On
On
30
9
7
MG.90.F2.22 - VLT is a registered Danfoss trademark
50