6-50 Terminal 42 Output
Option:
Function:
0mA
12 mA
20 mA
4mA
Par 4-17
(200%)
Par 4-16
(200%)
0% Torque
130BB372.10
Illustration 3.42
[150] Max Out Fr
4-20mA
0 Hz = 0 mA,
= 20
mA.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %
*
[0.00 -
200.00 %]
Scale for the minimum output (0 or 4
mA) of the analog signal at terminal 42.
Set the value to be the percentage of
the full range of the variable selected in
6-50 Terminal 42 Output
.
6-52 Terminal 42 Output Max Scale
Range:
Function:
100.00
%
*
[0.00 -
200.00 %]
Scale the maximum output of the selected
analog signal at terminal 42. Set the value
to the maximum value of the current signal
output. Scale the output to give a current
lower than 20 mA at full scale; or 20 mA at
an output below 100% of the maximum
signal value. If 20 mA is the desired output
current at a value between 0 - 100% of the
full-scale output, programme the
percentage value in the parameter, i.e. 50%
= 20 mA. If a current between 4 and 20 mA
is desired at maximum output (100%),
calculate the percentage value as follows:
20
mA / desired maximum current x 100 %
i.e. 10 mA : 20
10 x 100 = 200 %
130BA075.12
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Speed
(RPM)
Analogue
Output
Max Scale
par. 6-94
Illustration 3.43
6-53 Terminal 42 Output Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of Output 42 if
controlled by bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Holds the preset level of Output 42.
In case of a bus timeout and a timeout
function is selected in
6-50 Terminal 42
Output
the output will preset to this
level.
6-55 Analog Output Filter
Option: Function:
The following readout analog parameters from
selection in
have a filter
selected when
is on:
Selection
0-20 mA
4-20 mA
Motor current (0 - I
max
)
[103]
[133]
Torque limit (0 - T
lim
)
[104]
[134]
Rated torque (0 - T
nom
)
[105]
[135]
Power (0 - P
nom
)
[106]
[136]
Speed (0 - Speed
max
)
[107]
[137]
Table 3.20
[0]
*
Off Filter off
[1]
On Filter on
3.8.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Option:
Function:
Select the function of Terminal X30/8 as an
analog current output. Depending on the
selection the output is either a 0-20 mA or
4-20 mA output. The current value can be
read out in LCP in
[0]
*
No
operation
When no signal on the analog output.
[52]
MCO
0-20mA
[100] Output
frequency
0 Hz = 0 mA; 100 Hz = 20 mA.
[101] Reference
[Min - Max] 0% = 0 mA;
100% = 20 mA
[-Max - Max] -100% = 0
mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
94
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3