3-03 Maximum Reference
Range:
Function:
Size
related
*
[ par. 3-02 -
999999.999
ReferenceFeed-
backUnit]
Enter the Maximum Reference. The
Maximum Reference is the highest
value obtainable by summing all
references.
The Maximum Reference unit
matches:
•
The choice of configu-
ration in
for
[1] Speed closed loop
,
RPM; for
[2] Torque
, Nm.
•
The unit selected in
3-04 Reference Function
Option:
Function:
[0]
*
Sum
Sums both external and preset reference
sources.
[1]
External/Preset Use either the preset or the external
reference source.
Shift between external and preset via a
command or a digital input.
3.5.2 3-1* References
Select the preset reference(s). Select Preset ref. bit 0/1/2
[16], [17] or [18] for the corresponding digital inputs in
parameter group 5-1*.
3-10 Preset Reference
Array [8]
Range: 0-7
Range:
Function:
0.00
%
*
[-100.00 -
100.00 %]
Enter up to eight different preset references
(0-7) in this parameter, using array
programming. The preset reference is stated
as a percentage of the value Ref
MAX
) If a Ref
MIN
different from 0 (
) is
programmed, the preset reference is
calculated as a percentage of the full
reference range, i.e. on the basis of the
difference between Ref
MAX
and Ref
MIN
.
Afterwards, the value is added to Ref
MIN
.
When using preset references, select Preset
ref. bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in parameter
group 5-1*.
[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12 (+24V)
11001100
32
11110000
33
130BA149.10
Illustration 3.21
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 3.10 Preset Ref. Bit
3-11 Jog Speed [Hz]
Range:
Function:
Size related
*
[ 0.0 - par.
4-14 Hz]
The jog speed is a fixed output
speed at which the frequency
converter is running when the jog
function is activated.
See also
3-12 Catch up/slow Down Value
Range:
Function:
0.00
%
*
[0.00 -
100.00 %]
Enter a percentage (relative) value to be
either added to or deducted from the actual
reference for Catch up or Slow down respec-
tively. If
Catch up
is selected via one of the
digital inputs (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33 Digital Input
), the percentage
(relative) value is added to the total reference.
If
Slow down
is selected via one of the digital
inputs (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33 Digital Input
), the percentage
(relative) value is deducted from the total
reference. Obtain extended functionality with
the DigiPot function. See parameter group
3-9*
Digital Potentiometer
.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
57