1-21 Motor Power [HP]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00 hp]
Enter the nominal motor power in HP
according to the motor nameplate
data. The default value corresponds
to the nominal rated output of the
unit. This parameter is visible in LCP if
is
[1] US
1-22 Motor Voltage
Range:
Function:
Size related
*
[ 10. - 1000.
V]
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds
to the nominal rated output of the
unit.
1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000
Hz]
Min - Max motor frequency: 20-1000 Hz.
Select the motor frequency value from the
motor nameplate data. If a value different
from 50 Hz or 60 Hz is selected, it is
necessary to adapt the load independent
settings in
1-50 Motor Magnetisation at Zero
to
. For 87
Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt
4-13 Motor Speed High Limit [RPM]
and
to the 87 Hz
application.
1-24 Motor Current
Range:
Function:
Size related
*
[ 0.10 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. The data are used for
calculating torque, motor
protection etc.
1-25 Motor Nominal Speed
Range:
Function:
Size related
*
[10 - 60000
RPM]
Enter the nominal motor speed
value from the motor nameplate
data. The data are used for
calculating motor compensations.
n
m,n
= n
s
- n
slip
.
1-26 Motor Cont. Rated Torque
Range:
Function:
Size
related
*
[0.1 -
10000.0 Nm]
Enter the value from the motor
nameplate data. The default value
corresponds to the nominal rated
output. This parameter is available
when
is set to
1-26 Motor Cont. Rated Torque
Range:
Function:
[1] PM, non salient SPM
, i.e. the
parameter is valid for PM and non-
salient SPM motors only.
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
The AMA function optimises dynamic motor
performance by automatically optimising the
advanced motor parameters (
to
) at
motor standstill.
Activate the AMA function by pressing [Hand
on] after selecting [1] or [2]. See also the
section
Automatic Motor Adaptation
in the
Design Guide. After a normal sequence, the
display will read: "Press [OK] to finish AMA".
After pressing the [OK] key the frequency
converter is ready for operation.
[0]
*
Off
[1]
Enable
complete
AMA
Performs AMA of the stator resistance R
S
, the
rotor resistance R
r
, the stator leakage reactance
X
1
, the rotor leakage reactance X
2
and the
main reactance X
h
. Do
not
select this option if
an LC filter is used between the frequency
converter and the motor.
FC 301: The Complete AMA does not include
X
h
measurement for FC 301. Instead, the X
h
value is determined from the motor database.
R
S
is the best adjustment method (see
1-3*
Adv. Motor Data
).
T4/T5 E and F Frames, T7 D, E and F Frames
will only run a Reduced AMA when the
complete AMA is selected. It is recommended
to obtain the Advanced Motor Data from the
motor manufacturer to enter into
through
for best performance.
[2]
Enable
reduced
AMA
Performs a reduced AMA of the stator
resistance R
s
in the system only.
Note:
•
For the best adaptation of the frequency
converter, run AMA on a cold motor.
•
AMA cannot be performed while the motor is
running.
•
AMA cannot be performed on permanent magnet
motors.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
37