All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Range:
Function:
Size
related
*
[ 0.000 -
0.000 ]
Enter the value to define the duration
of the FALSE output from the
programmed timer. A timer is only
FALSE if it is started by an action (i.e.
Start timer 1 [29]
) and until the given
timer value has elapsed.
3.14.6 13-4* Logic Rules
Combine up to three boolean inputs (TRUE/FALSE inputs)
from timers, comtors, digital inputs, status bits and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
13-40 Logic Rule
Boolean 1
,
13-42 Logic Rule Boolean 2
and
13-44 Logic Rule
Boolean 3
. Define the operators used to logically combine
the selected inputs in
and
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.53
Priority of calculation
The results of
13-40 Logic Rule Boolean 1
,
and
13-42 Logic Rule Boolean 2
are calculated
first. The outcome (TRUE/FALSE) of this calculation is
combined with the settings of
and
13-44 Logic Rule Boolean 3
, yielding the final result
(TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
Select the first boolean (TRUE or
FALSE) input for the selected logic
rule.
See
([0] - [61])
and
([70] - [75])
for further description.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
122
MG33ME02 - VLT
®
is a registered Danfoss trademark