0-20 Display Line 1.1 Small
Option:
Function:
[1615]
Frequency [%]
Motor frequency, i.e. the output
frequency from the frequency
converter in percent.
[1616]
Torque [Nm]
Actual motor torque in Nm
[1617]
*
Speed [RPM]
Speed in RPM (revolutions per
minute) i.e. the motor shaft
speed in closed loop.
[1618]
Motor Thermal
Thermal load on the motor,
calculated by the ETR function.
[1619]
KTY sensor
temperature
[1620]
Motor Angle
[1621]
Torque [%] High Res.
[1622]
Torque [%]
Present motor load as a
percentage of the rated motor
torque.
[1625]
Torque [Nm] High
[1630]
DC Link Voltage
Intermediate circuit voltage in
the frequency converter.
[1632]
Brake Energy /s
Present brake power transferred
to an external brake resistor.
Stated as an instantaneous
value.
[1633]
Brake Energy /2 min
Brake power transferred to an
external brake resistor. The
mean power is calculated
continuously for the most recent
120 seconds.
[1634]
Heatsink Temp.
Present heat sink temperature of
the frequency converter. The
cut-out limit is 95 ±5° C; cutting
back in occurs at 70 ±5° C.
[1635]
Inverter Thermal
Percentage load of the inverters.
[1636]
Inv. Nom. Current
Nominal current of the
frequency converter.
[1637]
Inv. Max. Current
Maximum current of the
frequency converter.
[1638]
SL Controller State
State of the event executed by
the control.
[1639]
Control Card Temp.
Temperature of the control card.
[1648]
Speed Ref. After
Ramp [RPM]
[1650]
External Reference
Sum of the external reference as
a percentage, i.e. the sum of
analog/pulse/bus.
[1651]
Pulse Reference
Frequency in Hz connected to
the digital inputs (18, 19 or 32,
33).
0-20 Display Line 1.1 Small
Option:
Function:
[1652]
Feedback [Unit]
Reference value from
programmed digital input(s).
[1653]
Digi Pot Reference
[1657]
Feedback [RPM]
[1660]
Digital Input
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32 and
33). There are 16 bits in total,
but only six of them are used.
Input 18 corresponds to the
leftmost of the used bits. Signal
low = 0; Signal high = 1.
[1661]
Terminal 53 Switch
Setting
Setting of input terminal 54.
Current = 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either
as a reference or protection
value.
[1663]
Terminal 54 Switch
Setting
Setting of input terminal 54.
Current = 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either
as reference or protection value.
[1665]
Analog Output 42
[mA]
Actual value at output 42 in mA.
Use
to
select the value to be shown.
[1666]
Digital Output [bin]
Binary value of all digital
outputs.
[1667]
Freq. Input #29 [Hz]
Actual value of the frequency
applied at terminal 29 as an
impulse input.
[1668]
Freq. Input #33 [Hz]
Actual value of the frequency
applied at terminal 33 as an
impulse input.
[1669]
Pulse Output #27 [Hz] Actual value of impulses applied
to terminal 27 in digital output
mode.
[1670]
Pulse Output #29 [Hz] Actual value of impulses applied
to terminal 29 in digital output
mode.
[1671]
Relay Output [bin]
[1672]
Counter A
Application dependent (e.g. SLC
Control)
[1673]
Counter B
Application dependent (e.g. SLC
Control)
[1674]
Prec. Stop Counter
Display the actual counter value.
[1675]
Analog In X30/11
Actual value at input X30/11
either as reference or protection
value.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
28
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3