3.8.4 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for
analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par.
6-31 V]
Sets the analog input scaling value to
correspond to the low reference/
feedback value (set in
6-31 Terminal X30/11 High Voltage
Range:
Function:
10.00 V
*
[par. 6-30 -
10.00 V]
Sets the analog input scaling value to
correspond to the high reference/
feedback value (set in
).
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling
value to correspond to the low
voltage value (set in
).
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling
value to correspond to the high
voltage value (set in
6-31 Terminal X30/11 High
Voltage
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10.000 s] A 1
st
order digital low pass filter
time constant for suppressing
electrical noise on terminal X30/11.
NOTE
This parameter cannot be changed while the motor is
running.
3.8.5 6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for
analog input 4 (X30/12) placed on option module MCB
101.
6-40 Terminal X30/12 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par.
6-41 V]
Sets the analog input scaling value to
correspond to the low reference/
6-40 Terminal X30/12 Low Voltage
Range:
Function:
feedback value set in
6-41 Terminal X30/12 High Voltage
Range:
Function:
10.00 V
*
[par. 6-40 -
10.00 V]
Sets the analog input scaling value to
correspond to the high reference/
feedback value set in
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
Function:
0.000
*
[-999999.999 -
999999.999 ]
Sets the analog output scaling
value to correspond to the low
voltage value set in
.
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
Function:
100.000
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling
value to correspond to the high
voltage value set in
6-41 Terminal X30/12 High
Voltage
6-46 Term. X30/12 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10.000 s] A 1
st
order digital low pass filter
time constant for suppressing
electrical noise on terminal X30/12.
NOTE
This parameter cannot be changed while the motor is
running.
3.8.6 6-5* Analog Output 1
Parameters for configuring the scaling and limits for
analog output 1, i.e. Terminal 42. Analog outputs are
current outputs: 0/4 – 20 mA. Common terminal (terminal
39) is the same terminal and has the same electrical
potential for analog common and digital common
connection. Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an
analog current output. Depending on the
selection the output is either a 0-20 mA or
4-20 mA output. The current value can be
read out in LCP in
.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
92