4.1.25 35-** Sensor Input Option
Par.
No. #
Parameter description
Default value
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
35-0* Temp. Input Mode
35-00 Term. X48/4 Temp. Unit
[60] °C
All set-ups
TRUE
-
Uint8
35-01 Term. X48/4 Input Type
[0] Not Connected
All set-ups
TRUE
-
Uint8
35-02 Term. X48/7 Temp. Unit
[60] °C
All set-ups
TRUE
-
Uint8
35-03 Term. X48/7 Input Type
[0] Not Connected
All set-ups
TRUE
-
Uint8
35-04 Term. X48/10 Temp. Unit
[60] °C
All set-ups
TRUE
-
Uint8
35-05 Term. X48/10 Input Type
[0] Not Connected
All set-ups
TRUE
-
Uint8
35-06 Temperature Sensor Alarm Function
[5] Stop and trip
All set-ups
TRUE
-
Uint8
35-1* Temp. Input X48/4
35-14 Term. X48/4 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
35-15 Term. X48/4 Temp. Monitor
[0] Disabled
All set-ups
TRUE
-
Uint8
35-16 Term. X48/4 Low Temp. Limit
App.Dependent
All set-ups
TRUE
0
Int16
35-17 Term. X48/4 High Temp. Limit
App.Dependent
All set-ups
TRUE
0
Int16
35-2* Temp. Input X48/7
35-24 Term. X48/7 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
35-25 Term. X48/7 Temp. Monitor
[0] Disabled
All set-ups
TRUE
-
Uint8
35-26 Term. X48/7 Low Temp. Limit
App.Dependent
All set-ups
TRUE
0
Int16
35-27 Term. X48/7 High Temp. Limit
App.Dependent
All set-ups
TRUE
0
Int16
35-3* Temp. Input X48/10
35-34 Term. X48/10 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
35-35 Term. X48/10 Temp. Monitor
[0] Disabled
All set-ups
TRUE
-
Uint8
35-36 Term. X48/10 Low Temp. Limit
App.Dependent
All set-ups
TRUE
0
Int16
35-37 Term. X48/10 High Temp. Limit
App.Dependent
All set-ups
TRUE
0
Int16
35-4* Analog Input X48/2
35-42 Term. X48/2 Low Current
4.00 mA
All set-ups
TRUE
-5
Int16
35-43 Term. X48/2 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
35-44 Term. X48/2 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
35-45 Term. X48/2 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
35-46 Term. X48/2 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
Table 4.29
Parameter Lists
VLT
®
AutomationDrive Programmming Guide
194
MG33ME02 - VLT
®
is a registered Danfoss trademark
4