84
AK2-SC 255 Reference Manual
RS.8D.M1.22
Humidity adjusts target:
(List box: Yes, No) Whether or not humidity will adjust
the cooling target temperature.
Humidity sensor
(List box:)
Average: Cooling target modification will be based on
an average of two humidity sensors.
High: Cooling target modification will be based on the
highest of two humidity sensors.
Zone 1(etc.): (each zone humidty sensor will be
available as a choice in the list) Cooling target modifi-
cation will be based on the single selected sensor.
Dynamic offset
(-99.9 to 99.9) The number of degrees by which
humidity can adjust the target temperatures. Within the
range of humidity limiting the offset, a linear relation-
ship will exist between humidity and offset. (see also
next two parameters).
No offset <
(-99.9 to 99.9) The relative humidity below which
there will be no offset of target temperature.
Full >
(-99.9 to 99.9) The relative humidity above which the
maximum offset of target temperature by humidity will
be applied.
Ambient temp lockout
(List box: Yes, No) Whether or not cooling is to be
locked out below a set ambient temperature (next line).
No cooling below
(0.0 to 100.0) The ambient temperature below which
cooling will be locked out.
Night setback
(List box: Yes, No) Whether or not the cooling
setpoints are to be raised by an offset (next line) when
the store is closed according to a schedule or schedules
configured in the Store Info screens.
Night setback offset
(-50.0 to 50.0) The amount by which the cooling
setpoint (set on previous page) is to be raised during
store closed hours (as set in the Store Info screen.
Minimum ON time
(0 to 60) The minimum number of minutes cooling
must run after being turned on before being turned off.
Minimum OFF time
(0 to 60) The minimum number of minutes cooling
must remain off after being turned off before being
turned on.
Summary of Contents for AK2-SC 255
Page 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Page 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Page 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...