RS.8D.M1.22
AK2-SC 255 Reference Manual
103
Lockout above ambient
(0.0 to 150.0) The outside ambient temperature above
which auxiliary heat will be locked out.
Delay between stages
(0 to 99) The number of minutes after the start of an
auxiliary heat stage before the next stage can start.
Also, the minimum on time for every stage.
Analog gas valve
(List box: Yes, No) Whether or not the HVAC unit has
a controlled analog gas valve. [ClimaTECH controllers
have only one analog (variable) output. If a variable
speed fan is configured, an analog gas valve cannot be,
and vice versa.]
Temperature difference
(-40.0 to 150.0) the difference between supply air
temperature and zone temperature.
Min valve opening
(0 to 100) The minimum percentage of valve opening
when auxiliary heat is on.
Valve delay
(0 to 99) The number of seconds after the enabling
relay turns on before the analog valve can open.
ClimaTECH
dehumidification
configuration
Num of stages
(0 to 6) The number of dehumidification stages.
Occupied setpoint
(-40.0 to 150.0) The dehumidification setpoint during
operating hours as configured in the Store Info screen.
Unoccupied setpoint
(-40.0 to 150.0) The dehumidification setpoint during
store closed hours as configured in the Store Info
screen.
Lockout below ambient
(-40.0 to 150.0) The outside ambient temperature
below which dehumidification will be locked out.
Delay between stages
(0 to 99) The number of minutes after the start of a
dehumidification stage that must elapse before the next
stage can start. Also, the minimum time each stage
must run before being turned off.
Aux heat/dehumid lockout (List field: Yes, No) Whether or not auxiliary heat is to
be locked out when dehumidification is running. A yes
Summary of Contents for AK2-SC 255
Page 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Page 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Page 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...