78
AK2-SC 255 Reference Manual
RS.8D.M1.22
is less than this setpoint.
Speed:
Inverter
Min: (0.0 to 70.0) Max: (50.0 to 130.0) The highest
and lowest percent of rated maximum speed (last line
on the screen) that the inverter will be allowed to drive
the fan motor.
Heating
Min: (10.0 to 100.0) Max: (50.0 to 130.0) The highest
and lowest percent of rated maximum speed (last line
on the screen) that the inverter will be allowed to drive
the fan motor when heating is on.
Cooling
Min: (10.0 to 100.0) Max: (50.0 to 130.0) The highest
and lowest percent of rated maximum speed (last line
on the screen) that the inverter will be allowed to drive
the fan motor when cooling is on.
Dehumidification
Min: (10.0 to 100.0) Max: (50.0 to 130.0) The highest
and lowest percent of rated maximum speed (last line
on the screen) that the inverter will be allowed to drive
the fan motor when dehumidification is on.
Heat Reclaim in Dehum.
Min: (10.0 to 100.0) Max: (50.0 to 130.0) The highest
and lowest percent of rated maximum speed (last line
on the screen) that the inverter will be allowed to drive
the fan motor when dehumidification is being used for
dehumidification
.
Rpm at max speed
(1 to 9999) The rated maximum speed of the fan
motor, from the data plate.
Second page
AHU Fan
Configuration
Reaction Time
(1 to 20) This setting together with the next regulate
the sensitivity of speed control. These should be left at
the default settings and should only changed by a
Danfoss-trained technician.
Algorithm Interval
(1 to 15) This setting together with the preceding one
regulate the sensitivity of speed control. These should
be left at the default settings and should only changed
by a Danfoss-trained technician.
Inverter max resets
(0 to 10) The number of reset attempts, when proof is
not detected, before the variable speed drive will be
placed in override.
Inverter reset delay
(0 to 600) The number of seconds that must elapse
between resets.
Inverter proof delay
(0 to 600) The number of seconds that must elapse
after proof is not detected, before a reset attempt.
Monitor phase loss
(List box: Yes, No) Whether or not phase loss will be
monitored.
Shutdown on phase loss
(List box: Yes, No) Whether or not the unit is to be
shut down when its phase loss detector input is on.
Shutdown on smoke detect (List box: Yes, No) Whether or not the unit is to be
shut down when its smoke detector is on.
Shutdown on fire alarm
(List box: Yes, No) Whether or not the unit is to be
shut down when a monitored fire alarm occurs.
Summary of Contents for AK2-SC 255
Page 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Page 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Page 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...