RS.8D.M1.22
AK2-SC 255 Reference Manual
177
The Rescan Network button is used when nodes have been added to the network or
re-addressed. Until the network is rescanned, the new configuration will not be
recognized. After using the rescan button, the screen at right above appears.
List Points
Select List Points from the I/O Network Status Screen, and this is the screen that
appears:
The fields and their contents are as follows:
Bd-Pt
The address of the RO point to which the load is
wired, or, in the case of a received broadcast point,
the board and point address of the sending point.
The addresses may be in the form nn-n, or in the
form nn-n.n. These formats indicate, respectively,
Summary of Contents for AK2-SC 255