RS.8D.M1.22
AK2-SC 255 Reference Manual
151
Creating the
miscellaneous points
relay output
Exit to the Configure Miscellaneous menu, and from there select Relay Outputs and
press ENTER. The configuration screen for a relay output appears:
The first step in configuring a miscellaneous RO is to increase the field No. of relay
outputs by 1. In this example, we’re increasing 0 to 1 because this is the first miscella-
neous RO to be configured. Here’s what to do and where to do it:
Name
(Label, any 15 characters) Edit the field to read
appropriately to the purpose.
Bcast
(List box: No, Send, Rec) Leave the Bcast field set to
No. We are not going to use the point elsewhere on the
network.
Bd-Pt
(Bd-Pt label) In the Bd-Pt field, enter the number of
the board and terminals where the RO will be wired.
On
(List box: N-Closed, N-Open) Because the normal
state of the fan will be off, we will wire through the
normally open contacts for the output relay.
Notice the character > that is in reverse video in our example above. This is a button
field, and when it is selected, ENTER will take you to the next page. Initially, the
second page of this screen appears as at left below.