RS.8D.M1.22
AK2-SC 255 Reference Manual
99
Override switch
(List box: Yes, No) Whether or not there is an over-
ride switch wired to a digital input.
Override duration
(0 to 1439) The number of minutes that control will be
overridden after operation of the override switch.
Num of schedules
(0 to 8) The number of operating schedules entered
on the following page(s).
Seasons 4 password
(5-character auth code) The password given by
Seasons 4 to the equipment owner.
SC4condenser
configuration
Number of fans
(List box: None, Six, Eight) The number of HVAC
condenser fans controlled in this unit.
Minimum run time
(0 to 60) The number of minutes that a stage must run
before being turned off.
Liquid Temp Setpoint
(0.0 to 150.0, one setpoint per stage) The stage will be
turned on at setpoint plus range and turned off after
the stage above is turned off, at setpoint minus range.
Range
(0.0 to 150.0, one setpoint per stage) The stage will be
turned on at setpoint plus range and turned off after the
stage above is turned off, at setpoint minus range.
SC4 alarms
configuration
SC4 alarms are configured as are RTU alarms.
SC4 board & points
configuration
SC4 board & points are configured as are RTU board & points.
Summary of Contents for AK2-SC 255
Page 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Page 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Page 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...