26
AK2-SC 255 Reference Manual
RS.8D.M1.22
dewpoint sensors will be used.
Average: The average of a number of dewpoint
sensors will be used.
Dewpoint 1: A single dewpoint sensor will be used for
control.
[others]: Other dewpoint sensors, if they exist, will be
listed also.
Humidity sensor to use:
[If Calc Dewpoint has been selected](List box:) How
dewpoint will be determined if a humidity sensor is
used.
Min Humidity: The lowest-reading of a number of
humidity sensors will be used.
Max Humidity: The highest-reading of a number of
humidity sensors will be used.
Average: The average of a number of humidity
sensors will be used.
Inside RH 1: A single humidity sensor will be used
for control.
[others]: Other humidity sensors, if they exist, will be
listed also.
Auto defrost schedules
(List box: Disabled, Enabled)
Enabling this option will cause the controller to suggest
a defrost schedule based on the following two addi-
tional questions.
Maximum concurrent electric defrosts
[Appears only if Auto defrost schedules is enabled]
(0 to 20) The number of electric defrosts that can be
underway concurrently.
Include dripdown time
[Appears only if Auto defrost schedules is enabled]
(List box: Yes, No) Answering “Yes” will cause a drip
down period to follow defrost before refrigeration is
allowed. The length of the drip down period will be that
specified by the user when defrost schedules are auto-
configured.
Type
(List box:) [for each individual evaporator] the type of
evaporator control.
AK2-SC 255/SUBC: A subcooler controlled as an
SC 255 circuit.
AK2-SC 255: The circuit is controlled by the SC
255’s algorithms.
AKC 16x: Control is at the fixture by AKC 161 or
AKC 164 Smart Case Controllers.
EKC: Control is at the fixture by EKC 201 control-
lers.
Deg Master: Control is at the fixture by Hill/PHOE-
NIX Degree Master controllers.
DCU: Control is at the fixture by DCU case control-
lers.
Case lights button
In the lower left corner of the screen body is a button, CASE LIGHTS. Selecting this
button and pressing ENTER will open the configuration screen for a case lights
Summary of Contents for AK2-SC 255
Page 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Page 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Page 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Page 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...