The fields in this screen and their uses are as follows:
Clear Alarm Logs
In this SC 255 only, both the Active Alarms log and
the Cleared Alarms log will be cleared of entries.
Clear Network Log
Clears the Network alarms log (for the entire
AKCESS network).
Clear All SC 255 Logs Clears Active Alarms logs and Cleared Alarms logs
in all SC 255’s in the system.
Delete Alarm Config
Deletes the entire alarm configuration in this SC 255
only.
Send Test Alarm
Sends a single test alarm. The Generate system
test alarm function (see below) must be enabled.
Generate system test
alarm
Provides a means of generating a test alarm on a
regular schedule. You can select the days of the
week, the time of generation, and the alarm action
level. This function must be enabled with a schedule
which is true for the Send Test Alarm function to
operate.
Suspend alarm
generation
Suspends alarms. When you answer yes to this
question, another line will appear beneath it asking
you to specify a time period (from 1 to 255 hours)
during which no alarms will occur (effectively, all
alarms are disabled).