Test Operation
SiBE37-701
176
Test Operation
10.In case leak detection function not required
Press the
BS1 MODE
button once and the charging is complete.
Record the amount that was added on the additional refrigerant charge label provided with
the unit and attach it on the back side of the front panel.
Perform the test procedure as described in "Test operation" on page 184.
Charging in cooling mode
6.
Start up
Wait while the unit is preparing for charging in cooling mode.
It takes about 2 to 10 minutes for the system to become stable. In case of a small charging
amount, the system will start charging the refrigerant before the system reaches the stable
state. It may disturb a correct decision and may cause overcharging.
7.
Ready
Press the
BS4 TEST
button once within 5 minutes.
If the
BS4 TEST
button is not pushed within 5 minutes, "
P2
" will be displayed on the remote
controller. Refer to "Remote controller malfunction code display" on page 178.
8.
Operation
When the following LED display is shown, open valve A and close the front panel. If the front
panel is left open, the system can not operate properly during the refrigerant charging.
When the refrigerant tank is not connected or is left with the valve closed for 30 minutes or
more, the outdoor unit will stop operation and the "
P2
" code will be displayed on the remote
controller of the indoor unit. Follow the procedure as described in "Remote controller
malfunction code display" on page 178.
When a malfunction occurs, check the display of the remote controller and refer to "Remote
controller malfunction code display" on page 178.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Pressure control
(for the first minute)
Start up control
(for the next 2 minutes)
Waiting for stable
cooling conditions
(for the next ±15
minutes (according to
the system))
h j h h h h i
h j h h h i h
h j h h h i i
H1P
H2P
H3P
H4P
H5P
H6P
H7P
j j j h i h i
*
= The state of this LED is not important.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
*
*
*
*
*
i j
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...