Special Control
SiBE37-701
122
Function
3.3.2 Heating Oil Return Operation (including cooling / heating
simultaneous operation)
[Start conditions]
Referring to the following conditions, start heating oil return operation.
• Integral oil rise rate is reached to specified level.
• When cumulative compressor operating time exceeds 8 hours (2 hours when the power supply turns ON for
the first time)
Furthermore, the integral oil rise rate is calculated by Tc, Te, and compressor loads.
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the "Oil returning" process.
(Non-operating units stop while in "Preparation" mode.)
Actuator
Symbol
Elect. symbol
Oil return operation
REYQ
REMQ
Compressor 1
—
M1C
M1C
Maintain load that was applied before oil return
operation.
When current circulation rate < circulation rate required
for oil return operation, turn ON the STD compressor
every 10 seconds (up to 3 units at maximum).
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
When outdoor unit heat exchanger is condenser, the
fan will run under cooling fan control.
When outdoor unit heat exchanger is evaporator, the
fan will run at the fan step 7 or 8.
Outdoor unit fan 2
M2F
M2F
Electronic expansion valve (main)
EVM
Y1E
Y3E
Y1E
20SA=ON : PI control
20SA=OFF : 418pls
Electronic expansion valve
(subcooling)
EVT
Y2E
Y5E
Y3E
PI control
Electronic expansion valve (refilling
refrigerant)
EVJ
Y4E
Y2E
80pls
Four way valve (for heat changer
selection)
20SA
Y2S
Y9S
Y3S
When outdoor unit heat exchanger is condenser, the
valve will turn OFF.
When outdoor unit heat exchanger is evaporator, the
valve will turn ON.
Four way valve (for high- and low-
pressure gas pipe selection)
20SB
Y8S
Y2S
OFF
Solenoid valve (main bypass)
SVE
Y5S
Y10S
Y6S
OFF
Solenoid valve (hot gas)
SVP
Y4S
Y5S
0pls
Solenoid valve (liquid pipe of
refrigerant regulator)
SVL
Y3S
Y4S
0pls
Solenoid valve (gas discharge pipe of
refrigerant regulator)
SVG
Y1S
Y1S
0pls
Solenoid valve (drain pipe of
refrigerant regulator)
SVO
Y7S
Y7S
0pls
Solenoid valve (discharge pipe of
refrigerant regulator)
SVT
Y6S
Y8S
0pls
End conditions
•
Pe_min<0.22MPa
•
After a lapse of 9 min.
OR
or
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...