Troubleshooting by Indication on the Remote Controller
SiBE37-701
278
Troubleshooting
Troubleshooting
Ensure correct connection.
Ensure correct connection.
Replace the compressor.
Conclude the work
There is a possibility of defect
of pressure equalizing.
Check the refrigerant circuit.
Defect of pressure equalizing
Check the refrigerant circuit.
Replace the connecting wires and
ensure right connection of the
connector.
Local factor
Open the stop valve.
NO
NO
NO
NO
YES
NO
YES
NO
YES
NO
NO
NO
YES
YES
YES
YES
Check if
the stop valve is
open.
Power OFF
Power ON
Check if
the relay wires to the
compressor are
correct.
Check if the
connection of UVW
phase order is
correct.
Check if
the wiring is the
same as in the electric
wiring diagram.
The compressor
coil has disconnection
of wires.
Restart and
check the operation.
Check if the condition
occurs again.
Check if
the start mode is in
the high differential pressure
(not less than
0.5 MPa).
Check
if the inverter
output voltage between 3
phases is within
± 5V.
The insulation
resistance of the compressor
is low (not more than
100k
Ω
).
YES
YES
U
V
W
Check if the wiring has
any error in mistake for
inverter compressor.
Remove the connection between
the compressor and inverter. Set
the power transistor check mode
ON using “Setting mode 2” of the
outdoor unit PC board.
Measure the inverter output voltage
(
∗
2).
Note: Measurement should be made
while the frequency is stable.
Replace the inverter PC board.
Replace the inverter compressor.
∗
1: Pressure difference between high pressure and low pressure before starting.
∗
2: The quality of power transistors/ diode modules can be judged by executing
Check 4
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...