Field Setting
SiBE37-701
198
Test Operation
(18) Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries
out residual operation for one minute after the thermostat is stopped. (For the purpose of
preventing dust on the air filter from falling off.)
(19) Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
(20) Individual Setting of Ventilation
This is set to perform individual operation of heat reclaim ventilation using the remote controller/
central unit when heat reclaim ventilation is built in.
(Switch only when heat reclaim ventilation is built in.)
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
2
01
Without direct duct
connection
02
With direct duct
connection equipped
with fan
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
3
01
Individual operation of
humidifier
02
Interlocked operation
between humidifier and
drain pump
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
5
01
—
02
Individual operation of
ventilation
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...