Test Operation
SiBE37-701
180
Test Operation
1.2.6 Before operation
1.2.6.1
Service precautions
WARNING: ELECTRIC SHOCK
Caution when performing service to inverter equipment
1. Do not open the electric box cover for 10 minutes after the power supply is turned off.
2. Measure the voltage between terminals on the terminal block for power supply with a tester
and confirm that the power supply is shut off.
In addition, measure the points, as shown in the figure below, with a tester and confirm that
the voltage of the capacitor in the main circuit is less than 50 V DC.
3. To prevent damaging the PC-board, touch a noncoated metal part to eliminate static
electricity before pulling out or plugging in connectors.
4. The performing of the service to the inverter equipment must be started after the junction
connectors X1A, X2A, X3A, X4A (X3A and X4A are for 14~16 unit type only) for the fan
motors in the outdoor unit are been pulled out. Be careful not to touch the live parts.
(If a fan rotates due to strong wind, it may store electricity in the capacitor or in the main
circuit and cause electric shock.)
5. After the service is finished, plug the junction connecter back in. Otherwise the error code
E7
will be displayed on the remote controller and normal operation will not be performed.
For details refer to the wiring diagram labelled on the back of the electric box cover.
Pay attention to the fan.
It is dangerous to inspect the unit while the fan is running. Be sure to
turn off the main switch and to remove the fuses from the control circuit located in the outdoor
unit.
Note:
Play it safe!
For protection of the PCB, touch the switch box casing by hand in order to eliminate static
electricity from your body before performing service.
1.2.6.2
Checks before initial start-up
Note:
Remark that during the first running period of the unit, required power input may be higher than
stated on the nameplate of the unit. This phenomenon originates from the compressor that
needs elapse of a 50 hours run in period before reaching smooth operation and stable power
consumption.
Make sure that the circuit breaker on the power supply panel of the installation is switched
off.
Attach the power wire securely.
Introducing power with a missing N-phase or with a mistaken N-phase will break the
equipment.
A2P
A1P
A3P
TP1 TP2
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...