SiBE37-701
Test Operation
Test Operation
161
[Special notice of product]
CLASSIFICATION
This air conditioner comes under the term “appliances not accessible to the general public”.
EMC CHARACTERISTICS
VRVIII System is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
REFRIGERANT
VRVIII System use R-410A refrigerant.
z
The refrigerant R-410A requires strict cautions for keeping the system clean, dry and tight.
Read the chapter “REFRIGERANT PIPING” carefully and follow these procedures correctly.
A.Clean and dry
Foreign materials (including mineral oils such as SUNISO oil or moisture) should be
prevented from getting mixed into the system.
B.Tight
Take care to keep the system tight when installing.
R-410A does not contain any chlorine, does not destroy the ozone layer, and does not
reduce the earth’s protection against harmful ultraviolet radiation.
R-410A can contribute slightly to the greenhouse effect if it is released.
z
Since R-410A is a mixed refrigerant, the required additional refrigerant must be charged in
its liquid state. If the refrigerant is charged in a state of gas, its composition changes and the
system will not work properly.
Limit by the total maximum refrigerant charge
The total maximum refrigerant charge of a VRVIII system must be below 100kg, this to be in
accordance with CE requirement (EN60335-2-40 standard).
This means that in case the total maximum refrigerant charge of the system (factory and
additional charge) is equal to or more than 100kg you must divide your multiple outdoor system
into smaller independent systems, each containing less than 100kg refrigerant charge.
For factory charge, refer to the unit name plate.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent
gases into the atmosphere.
Refrigerant type : R-410A
GWP
(1)
value : 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
the factory refrigerant charge of the product,
the additional refrigerant amount charged in the field and
+
the total refrigerant charge on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto
the inside of the service cover).
(2)
In case of multiple outdoor systems, only 1 label must be adhered, mentioning the total
factory refrigerant charge of all outdoor units connected on the refrigerant system.
DESIGN PRESSURE
Since design pressure is 4.0MPa or 40bar (for R-407C units : 3.3MPa or 33bar), the wall
thickness of pipes should be more carefully selected in accordance with the relevant local and
national regulations.
1
factory refrigerant charge of the
product : see unit name plate
(2)
2
additional refrigerant amount
charged in the field
3
total refrigerant charge
4
Contains fluorinated greenhouse
gases covered by the Kyoto Protocol
5
outdoor unit
6
refrigerant cylinder and manifold for
charging
3
5
6
2
1
4
-
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...