SiBE37-701
Outline of Control (Indoor Unit)
Function
143
6.2.2 Thermostat Control while in Normal Operation
VRV multi systems are set at factory to thermostat control mode using the remote controller.
While in normal thermostat differential control mode (i.e., factory set mode), the thermostat
turns OFF when the system reaches a temperature of -1°C from the set temperature while in
cooling operation or of +1°C from that while in heating operation.
While in a single remote controller group control, the body thermostat is only used for this
control.
Furthermore, while in heating operation, cassette-mounted indoor units conduct the thermostat
control by a value compensated by -2°C for the value detected with the body thermostat.
(Through field settings, the thermostat differential setting can be changed from 1°C to 0.5°C.
For details on the changing procedure, refer to information on page onward.)
6.2.3 Thermostat Control in Dry Operation
While in dry operation, the thermostat control is conducted according to a suction temperature
at the time of starting the dry operation.
Assuming that the suction air temperature at the time of starting the dry operation is Tro and the
suction air temperature in operation is Tr,
Furthermore, while in dry operation mode, fans operate at L flow rate, stops for a period of six
minutes while the thermostat is OFF, and then return to operation at L flow rate. (This control is
used to prevent a rise in indoor temperature while in thermostat OFF mode.)
Cooling operation:
Heating operation:
Normal
operation
Thermostat OFF
Tr < Set temperature -1
ºC
Normal
operation
Thermostat OFF
Tr > Set tempe1
º
C
Tr: Temperature detected with the suction
air thermistor (R1T)
when Tro
≤
24.5
º
C:
when Tro > 24.5
º
C:
In dry operation
In dry operation
Tr < Tro - 1
º
C
Tr < Tro - 1.5
º
C
Thermostat OFF
Thermostat OFF
Tro: Suction air temperature at the
time of starting the dry operation
Tr: Temperature detected with the
suction air thermistor (R1T)
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...