Field Setting
SiBE37-701
230
Test Operation
3.2.10 Prevention of Micro Heating in Non-operating Unit
In heating operation, this setting is made to prevent room temperature from rising due to micro
heating capacity generated in the unit with its heating thermostat OFF or in the unit with its
heating operation stopped.
•
By switching the BS units to cooling when the system turns OFF the heating thermostat or
stops heating operation, micro heating is prevented.
•
By enabling the micro heating prevention setting of the outdoor unit, prevention of micro
heating of all BS units connected to the outdoor unit is enabled. (Default setting of BS unit)
•
Setting by BS unit is enabled by changing the micro heating prevention setting of every BS
unit. (In this case, enable the outdoor unit setting.)
3.2.11 Reduction of Cooling/Heating Selection Time of BS Units
Make this setting to reduce selection time between cooling and heating of the BS units, with
careful attention paid to the following points.
•
This setting is only enabled in case the refrigerant piping length between every BS unit
connected to the outdoor unit and the indoor unit is not more than 10 m. (Refer to the figure
shown below: (a)
≤
10 m and (b)+(c)
≤
10 m and
…
)
•
In case the refrigerant piping length between the BS units and the indoor units is long,
refrigerant passing sounds may become louder when the BS unit selects operation mode
between cooling and heating.
•
This setting reduces the operation mode selection time in all the BS units within the same
refrigerant circuit.
BS unit
Outdoor unit
a
Indoor unit
BS unit
b
Indoor unit
Indoor unit
c
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...