Troubleshooting by Indication on the Remote Controller
SiBE37-701
334
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
NO
YES
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
YES
YES
NO
YES
(
Go on to the next page.
LED lamp display
)
Check the detailed malfunction
status in the monitor mode.
(Refer to P250~251 for how to
check.)
Reset the power supply here.
In Check 4,
LED lamp indicates
as follows:
Check if
indoor unit PC board or
outdoor unit PC board has been replaced.
Or check if indoor/ outdoor, outdoor/
outdoor connecting wires
are normal.
Check if all
the indoor remote controllers
within the same refrigerant
circuit display
“U4”.
Check if the
indoor/ outdoor, outdoor/
outdoor connecting wires
are normal.
Check if the
voltage between RS
terminals on the outdoor unit
PC board is 200V.
The fuse on
the outdoor unit PC
board is blown.
Check if
the normal condition
monitor for the microcomputer
(HAP) on the outdoor unit
PC board blinks.
Check if
the LED in preparation
mode (H2P) on the outdoor
unit PC board
blink.
Lights do not
go out for 12 minutes
or more.
Check if
the indoor/ outdoor,
outdoor/ outdoor connecting
wires are normal.
Check if
the operation is normal
with 1 circuit after outdoor/ outdoor
connecting wires are
removed.
Press the rewiring button on the
main PC board of the master
outdoor unit. Keep pressing for 5
seconds or more. (Operation does
not start for a maximum 12
minutes.)
Replace indoor unit PC board.
Correct the connecting wires.
Correct the voltage (200V).
Replace the fuse.
Replace the outdoor unit PC
board.
Press the rewiring button on the
main PC board of the outdoor unit.
Keep pressing for 5 seconds or
more.
Correct the connecting wires.
Replace the main PC board of
outdoor unit.
Fix DIII Net extension adapter.
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...