Troubleshooting by Indication on the Remote Controller
SiBE37-701
274
Troubleshooting
Troubleshooting
NO
YES
YES
YES
NO
NO
YES
NO
Check for the points shown below.
Is the stop valve open?
Is the HPS connector properly connected to the
main PC board?
Does the high pressure switch have continuity?
Are the
three points above
OK?
Rectify defective points, if any.
NO
YES
Check if the
“high pressure” value and
the actual measurement value by
pressure sensor are
the same.
Replace main PC board ( A1P).
Mount a pressure gauge on the high-pressure
service port.
Reset the operation using the remote controller,
and then restart the operation.
Does the stop
due to malfunction (E3)
recur?
Is the HPS
operating value normal
(i.e., 4.0MPa)?
Are the
characteristics of the high
pressure sensor normal?
(See
∗
1.)
Replace the HPS.
Replace the high pressure sensor.
· The high pressure sensor is normal, and the pressure detected with the PC board is also normal.
· The high pressure has really become high.
CHECK 5
Referring to information on P372, remove the causes by
which the high pressure has become high.
∗
1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on P439.)
∗
2: Make measurement of voltage of the pressure sensor.
+5V
(4)
(3)
(2)
(1)
Connector for high
pressure sensor (Red)
High
pressure
sensor
Micro controller
A/D input
Make measurement of DC
voltage between these wires.
Red
Black
White
Connect the service checker to compare the “high pressure” value and the
actual measurement value by pressure sensor (Refer to
∗
1) by using the
service checker.
Service Checker
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...