Test Operation
SiBE37-701
174
Test Operation
Note:
For a multi outdoor unit system, it is not required to connect all charge ports to a refrigerant
tank.
The refrigerant will be charged with ±30 kg in 1 hour time at an outdoor temperature of 30°C DB
or with ±12 kg at an outdoor temperature of 0°C DB.
If you need to speed up in case of a multiple outdoor system, connect the refrigerant tanks to
each outdoor unit as shown in figure on page 173.
1. Start of automatic charging refrigerant
- Open the liquid pipe, suction gas pipe, high pressure/low pressure gas pipe and equalizer
pipe stop valves and the service port stop valve. (Valves A, B and C must be closed.)
- Close all front panels except the electric component box front panel and turn the power
ON.
- Make sure all indoor units are connected, refer to "How to check how many units are
connected" on page 179.
- If the H2P LED is not flashing (in 12 minutes time after turning on the power), make sure it
is displayed as shown in the "Normal system display" on page 177.
If the H2P LED is flashing, check the malfunction code on the remote controller " Remote
controller malfunction code display" on page 178.
If you perform the refrigerant charging operation within the refrigerant system with one or
more units with power OFF, the refrigerant charging operation can not be accomplished
properly.
For confirming the number of indoor units with power ON, refer to "How to check how many
units are connected" on page 179.
In case of a multi system, turn the power ON to all outdoor units in the refrigerant system.
To energize the crankcase heater, make sure to turn the power ON at least 6 hours before
starting operation.
2.
Press the
BS1 MODE
button once if the LEDs combination is not as in the figure below.
3.
Press the
BS4 TEST
button once.
4.
Hold the
BS4 TEST
button down for 5 seconds or more.
5. Charging mode judgement
However, if the indoor temperature is 10°C DB or lower, in some cases the unit will charge in
heating mode to increase the indoor temperature.
The unit will automatically select the cooling mode or heating mode for charging.
When charging in cooling mode, the unit will stop operating when the required amount of
refrigerant is charged.
During charging in heating mode, a person must manually close valve A before complete
charging is finished. The required amount is the calculated amount (see "6. Example of
connection" on page 433), therefore, the weight must be monitored constantly.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
h h i h h h h
H1P
H2P
H3P
H4P
H5P
H6P
H7P
i i i i i i i
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...