Test Operation
SiBE37-701
170
Test Operation
[Remote controller displays malfunction code]
Note:
If any malfunction codes other than the above are displayed, check the service manual for how
to respond.
1.2.5.2.3 TEST RUN
1. Before test run
z
Make sure the following works are completed in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Additional refrigerant charge
Check operation
z
Check that all work for the BS, indoor unit are finished and there are no danger to operate.
2. Test Run
After all works are completed, operate the unit normally and check the following.
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corresponding outdoor unit is also
operating.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller to see if they operate
properly.
Note:
z
Heating is not possible if the outdoor temperature is 24°C or higher. Refer to the Operation
manual.
z
If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
z
Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button
of the remote controller is pushed.
z
When the system operation is stopped by the remote controller, the outdoor units may
continue operating for further 5 minutes at maximum.
z
The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not a malfunction.
Malfunction
code
Installation error
Remedial action
E3, E4
F3, F6
UF
The shutoff valve of the outdoor unit is
left closed.
Open the shutoff valve.
U1
The phases of the power to the outdoor
unit is reversed.
Exchange two of the three phases (L1, L2, L3) to make
a proper connection.
U1
U4
LC
No power is supplied to an outdoor, BS
or indoor unit (including phase
interruption).
Make sure the power source wire is properly connected
to the outdoor, BS or indoor unit and revise if necessary.
UF
There is conflict on the connection of
transmission wiring in the system.
Check if the refrigerant piping line and the transmission
wiring are consistent with each other.
E3
F6
UF
Refrigerant overcharge.
Recalculate the additional amount refrigerant from the
piping length and correct the refrigerant charge level by
recovering any excessive refrigerant with a refrigerant
recovery machine.
E4
F3
Insufficient refrigerant.
z
Check if the additional refrigerant charge has been
finished correctly.
z
Recalculate the additional amount
refrigerant from the piping length and add the
adequate amount.
U7, U4
UF, UH
Field wiring is connected to “TO MULTI
UNIT (Q1,Q2)” terminal on the outdoor
unit PC-board (A1P) when the system is
one outdoor system.
Remove the line from the “TO MULTI UNIT (Q1, Q2)”
terminal.
UA
The internal transmission wiring to “TO
MULTI UNIT (Q1,Q2)” for the single
outdoor unit system are disconnected.
Connect the internal transmission wiring to “TO MULTI
UNIT (Q1,Q2)”. (See the wiring diagram.)
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...