109
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.4.4 Alarm for low difference between high and low pressure
Checking of the difference between high and low pressure values takes place when at least one compressor of the circuit
involved is running.
Upon compressor start-up, a certain difference must be generated between high and low pressure in order to ensure correct
compressor rotation and oil return to the compressor.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
PAL92
3.00
bar
Low pressure difference alarm threshold
PAL93
60
s
Low pressure difference alarm delay on starting of compressors
PAL94
90
s
Low pressure difference alarm delay at steady state
PAL95
2
-
Maximum number of alarms in one hour due to low pressure difference
Alarm code
AL114 for circuit 1; AL115 for circuit 2
Reason for activation
Upon start-up of one compressor in the circuit, if the pressure difference is <= than PAL92
for the number of seconds set in PAL93
After the time in PAL93 has elapsed, if the pressure difference is <= than PAL92 for the
seconds set in PAL94
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL95”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
4.4.5 Low superheating alarm
Where an electronic expansion valve is fitted, the controller manages the superheating of the intake gas to the compressor.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
Et30
300
s
Low superheating alarm delay
Et37
2.0
°C
Low superheating protection threshold
PAL4
5
-
Maximum number of alarms in one hour due to low pressure
Alarm code
AL170 for circuit 1; AL171 for circuit 2
Reason for activation
If the measured superheating value is lower than threshold ET37 for a time longer than the
setpoint in parameter ET30
Reset
When the measured superheating value is higher than or equal to threshold ET37 +1°C for
1 second
Reset mode
Automatic until the number of trip occurrences in one hour set in parameter PAL4 is rea
-
ched
Manual as soon as the number of trip occurrences in one hour set in parameter PAL4 is
exceeded
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...