103
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
CPY humidifier – Communication error alarm
Alarm code
AL164
Reason for activation
Communication error with CPY board
Reset
As soon as serial communication with CPY board is restored.
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Humidifier
According to parameters set in CPY board
The other devices
They follow their control
4.3.4 Heater alarms
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
PAL34
5
s
Activation delay
PAL35
5
-
Max. number of alarms in one hour
Thermal overload switch
Alarm code
AL250 for heater 1; AL251 for heater 2
Reason for activation
Upon opening of the relevant digital input after the delay set in parameter “PAL34”
Reset
As soon as the relevant digital input closes.
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL35”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Heaters
The controller stops the involved heaters.
The other devices
They follow their control
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...