90
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.1.2 File “alarm.conf”
This file is used to customise management of each alarm according to:
-
the seriousness of the alarm, based on which a digital output is associated;
-
the alarm being enabled with the unit off;
As regards the alarm seriousness, the available selections affect the closing of digital outputs and they include:
-
0 = no warning message;
-
1 = non serious alarm designed to trigger activation of corresponding digital output;
-
2 = serious alarm designed to trigger activation of corresponding digital output;
-
3 = serious alarm designed to trigger activation of both digital outputs.
The options for the alarm with the unit off include:
-
0 = alarm enabled;
-
1 = alarm disabled.
The file can be accessed and edited using any text editor.
Refer to the chapter on programming procedures for the upload of the “alarm.conf” file into the controller and its editing.
4 Alarms