5.3 Change of set points
5.3.1 Setpoint editing from display
Go to the main menu and press “Setpoint” to access the screens where functions are displayed whose setpoints need to
be managed.
Go to the “Setpoint” sub menu and select the function whose setpoint is to be changed.
Scroll the parameters until the desired parameter setpoint is achieved.
Select the setpoint parameter to enable the edit keypad.
Set the new value and apply the green tick to confirm.
Units featuring mode switching have a setpoint for cooling “ST7” and a setpoint for heating “STH7”.
The setpoint for cooling “ST7” must necessarily be higher than the setpoint for heating “STH7”.
5.3.2 Setpoint editing from BMS
Setpoints can be edited from the BMS only if this function is enabled.
See dedicated BMS management document.
5.4 Change language
When in the main menu, press “Languages” to access the screens in which the available languages are displayed.
If the language you are looking for is not in the screen, use the arrows to find it.
The selected language becomes active as soon as it is selected.
5 Faq
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...