104
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.3.5 Defrost cycle ended due to max. time achieved
Alarm code
AL184 for circuit 1; AL185 for circuit 2
Reason for activation
If a defrost ends due to time limit instead of due to condensing temperature threshold
Reset
Automatic
Reset mode
At the next defrost ended with exceeding of the condensation threshold
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
The other circuits and
devices
They follow their control
4.3.6 “Leak detector” alarms
Refrigerant leak alarm
Alarm code
AL154
Reason for activation
After the time set in parameter “PAL21”, when the refrigerant detector warns about a leak.
Reset
Always manual with parameter “PAL23” = “0”
Reset mode
Manual
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Dampers and ventilation
When operating fully with outside air and if the digital OK signal for one area damper and
additional ventilation are not featured in the unit.
Other devices
All disabled
Refrigerant leak sensor - Malfunction alarm
Alarm code
AL151
Reason for activation
When the controller identifies a sensor malfunction.
Reset
After the sensor is back to normal operating conditions.
Reset mode
Manual
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Dampers and ventilation
When operating fully with outside air and if the digital OK signal for one area damper and
additional ventilation are not featured in the unit.
Other devices
They follow their control
Refrigerant leak sensor - Maintenance almost required
Alarm code
AL152
Reason for activation
Sensor replacement is close to being needed.
Reset
After sensor replacement
Reset mode
Manual
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Other devices
Warning only (all devices follow their setting)
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...