41
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
3.9.8 Ventilation in return line
The table shows the ventilation parameters for the various functions connected.
Parameter Min
Max
UM
Description
RFA4
0
999
s
Delay time to fan switch-off
RFA6
0
999
s
Delay time to return fan switch-on from On unit
RFA7
0
100
%
Minimum speed
RFA8
15
100
%
Maximum speed
RFA9
0
100
%
Manual override (0 = Disabled)
RFA11
375
900
10 m
3
/h Fixed speed in de-humidification mode (0 = Disabled)
RFA25
375
900
10 m
3
/h Leak detector - Flow rate setpoint
RFA26
375
900
10 m
3
/h PID - Constant air flow control - Flow rate setpoint
RFA27
0
900
10 m
3
/h PID - Constant air flow / pecentage air flow control - Min. flow rate setpoint
RFA28
375
9999
10 m
3
/h PID - Constant air flow / pecentage air flow control - Max. flow rate setpoint
RFA29
0
9999
10 m
3
/h PID - Constant air flow control - New air flow setpoint when the temperature
setpoint is reached
RFA30
0
1
-
PID - Constant air flow control - Enabling of new air flow setpoint when the
temperature setpoint is reached
RFA31
0
9999
10 m
3
/h PID - Constant air flow control - Defrost - New air flow setpoint
RFA32
0
1
-
PID - Constant air flow control - Defrost - Enabling of new air flow setpoint
RFA33
10.0
100.0
Pa
Constant pressure control - Pressure setpoint
RFA34
0.0
100.0
Pa
Constant pressure control - Min. pressure setpoint
RFA35
10.0
3270.0 Pa
Constant pressure control - Max. pressure setpoint
RFA36
0.0
3270.0 Pa
Constant pressure control - Neutral area
RFA37
0.0
3270.0 Pa
Constant pressure control - Differential required for decrement
RFA38
0.0
3270.0 Pa
Constant pressure control - Differential required for increment
RFA39
15
999
s
Constant pressure control - Max. increment time
RFA40
0
60
s
Constant pressure control - Min. increment time
RFA41
15
999
s
Constant pressure control - Max. decrement time
RFA42
0
60
s
Constant pressure control - Min. decrement time
RFA43
1
100
%
Constant pressure control - Max. increment amplitude
RFA44
0
5
%
Constant pressure control - Min. increment amplitude
RFA45
1
100
%
Constant pressure control - Max. decrement amplitude
RFA46
0
5
%
Constant pressure control - Min. decrement amplitude
RFA47
0
9999
10h
Threshold for “fan operating hours exceeded” alarm (0 = Disabled)
RFA49
-50.0
50.0
Pa
Constant pressure difference control - Pressure delta setpoint
RFA50
-3270.0 50.0
Pa
Constant pressure difference control - Min. pressure difference setpoint
RFA51
-50.0
3270.0 Pa
Constant pressure difference control - Max. pressure difference setpoint
RFA52
0.0
3270.0 Pa
Constant pressure difference control - Neutral area
RFA53
0.0
3270.0 Pa
Constant pressure difference control - Differential required for decrement
RFA54
0.0
3270.0 Pa
Constant pressure difference control - Differential required for increment
RFA55
15
999
s
Constant pressure difference control - Max. increment time
RFA56
0
60
s
Constant pressure difference control - Min. increment time
RFA57
15
999
s
Constant pressure difference control - Max. decrement time
RFA58
0
60
s
Constant pressure difference control - Min. decrement time
RFA59
1
100
%
Constant pressure difference control - Max. increment amplitude
RFA60
0
5
%
Constant pressure difference control - Min. increment amplitude
RFA61
1
100
%
Constant pressure difference control - Max. decrement amplitude
RFA62
0
5
%
Constant pressure difference control - Min. decrement amplitude
RFA67
0
10000
-
PID - Constant air flow / pecentage air flow control - Kp
RFA68
0
10000
-
PID - Constant air flow / pecentage air flow control - Ki
RFA69
0
10000
-
PID - Constant air flow / pecentage air flow control - Kd
3 Software functions
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...