88
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
3.19 Enabled functions
The controller offers the opportunity to enable some functions that are managed by the software.
The parameters concerned are shown in the table.
Parameter Min
Max
UM
Description
SP37
0
1
-
Enable heater 1
SP38
0
1
-
Enable heater 2
SP39
0
1
-
Enable fire / smoke alarm
SP46
0
1
-
Enable static pressure / differential pressure probe
SP48
0
1
-
Enable CO2 air quality probe
3.19.1 Option management
The unit may be fitted with some options.
After installation, option management must be enabled in the controller.
Refer to the instructions supplied with the installation kit and to the wiring diagram for the necessary connections.
Options that require enabling in the controller include:
-
heaters;
-
fire/smoke alarm;
-
static pressure/differential pressure probe;
-
CO
2
air quality probe.
These functions are enabled in the screens containing the “SP - Setup” parameters. Access to these screens requires entry
of “Service” credentials.
When a function is enabled, the inputs and outputs required for operation are automatically activated.
Refer to the instructions supplied with the option for the installation procedure. Refer to the wiring diagram for the electrical
connections.
The controller must be restarted to make any change active.
When an option is enabled, a request for controller restart appears automatically in the form of a message on the display.
A countdown appears in the message window, which can be bypassed - the restart procedure is started immediately - or
delayed. If none of the two actions above is selected, the controller gets restarted at the end of the countdown.
If the restart procedure is delayed, the controller will automatically display a restart message after a few seconds.
The controller may also be restarted by de-energising and then re-energising it.
3 Software functions
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...