106
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.4 Circuit alarms
The circuit alarms occur only on the compressors of the circuit involved.
4.4.1 High-pressure alarms
The delivery pressure in each refrigerant circuit is controlled by safety pressure switches and by pressure transducers.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
PAL11
39.00
bar
High pressure alarm threshold
PAL12
4.00
bar
High pressure alarm differential
PAL13
0
-
Maximum number of alarms in one hour due to high pressure
Pressure switch high pressure alarm
Alarm code
AL6 for circuit 1; AL7 for circuit 2
Reason for activation
With the unit running, when the digital input opens to which the relevant safety devices are
connected
Reset
When the relevant digital input closes
Reset mode
Manual
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
High pressure alarm from transducers
Alarm code
AL10 for circuit 1 and AL11 for circuit 2
Reason for activation
With unit running, if the value measured by the pressure probe is >=PAL11
Reset
When the value measured by the pressure probe is <= (PAL11 - PAL12)
Reset mode
Automatic, and becomes manual after PAL13 occurrences/hour
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
4.4.2 Low pressure alarms
The intake pressure in each refrigerant circuit is controlled by low pressure switches and transducers.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
PAL1
15
s
Low pressure alarm delay on starting of the circuit
PAL2
4.5
bar
Low pressure alarm threshold during operation
PAL3
2.0
bar
Low pressure alarm differential during operation
PAL4
5
-
Maximum number of alarms in one hour due to low pressure
PAL10
5
s
Low pressure alarm delay at full operating speed
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...