113
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
Exhaust gas temperature
Alarm code
AL61 for circuit 1, compressor 1; AL62 for circuit 2, compressor 1; AL63 for
circuit 1, compressor 2; AL64 for circuit 2, compressor 2.
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
Intake temperature
Alarm code
AL102 for circuit 1; and AL103 for circuit 2
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...