17
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
The value set in parameter “ST9” determines which control probe is to be used:
-
0 = temperature probe on air delivery line;
-
1 = temperature probe on air return line;
The value set in parameter “ST11” determines the type of temperature control, as follows:
-
0 = proportional.
-
1 = "Cascade";
-
2 = PID.
3.3.1 Thermoregulation in cooling mode
The thermoregulation of the unit depends on parameter “ST9”, which identifies the reference probe for the temperature
setpoint (parameter “ST1”), and on parameter “ST11” which determines the type of temperature/humidity control.
In proportional control mode, the controller activates the available resources as the value read by the reference probe in
-
creases in comparison to the setpoint value.
When “Cascade” temperature/humidity control is selected, the controller uses it to enable the resources and at the same
time monitor the air temperature in the delivery line.
In PID control mode, the controller activates the available resources as the demand increases. The controller calculates the
demand and checks the value measured by the probe against the setpoint value and according to its variation over time
using the parameters set in the PID.
Proportional temperature control
If parameter “ST11” is set to “0”, proportional control is enabled.
The parameters involved in proportional temperature control are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
ST1
24.0
°C
Temperature setpoint
ST2
18.0
°C
Min. air temperature setpoint
ST3
28.0
°C
Max. air temperature setpoint
ST4
2.0
°C
Proportional control - Cooling - Activation differential
ST5
0.1
°C
Proportional control - Cooling - Neutral activation area
ST6
0.1
°C
Proportional control - Cooling - Offset
A graphical representation is shown below.
ST5
ST6
ST4
100
0
%
ST1
SdR °C
Fig. 4 Graphical representation of cooling demand
In addition to the parameters listed in the table, the abbreviations in the graph are:
-
SdR = reference probe;
-
% = percentage demand value.
3 Software functions
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...