96
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.2.7 Thermal overload switch alarm in ventilation unit
Ventilation in delivery line - Thermal overload switch alarm
Alarm code
AL35
Reason for activation
When the system demands ventilation unit activation and the digital input corresponding to
the alarm is open after the time set in parameter “PAL25” has elapsed
Reset
When the digital input closes
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL26”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
The controller stops the operation of the unit.
Ventilation in return line - Thermal overload switch alarm
Alarm code
AL36
Reason for activation
When the system demands ventilation unit activation and the digital input corresponding to
the alarm is open after the time set in parameter “PAL25” has elapsed
Reset
When the digital input closes
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL26”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
The controller stops operation of the fans in the return line.
External ventilation - Thermal overload switch alarm
Alarm code
AL33 for circuit 1; AL34 for circuit 2
Reason for activation
When the system demands ventilation unit activation and the digital input corresponding to
the alarm is open after the time set in parameter “PAL47” has elapsed.
Reset
When the digital input closes
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL48”.
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Source-side fans
The alarm is displayed for warning purposes only. The fans concerned are stopped
electro-mechanically.
The other devices
They follow their control
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...