102
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.3.2 Electronic valve driver alarm
Communication error alarm
Alarm code
AL160 for circuit 1; AL161 for circuit 2
Reason for activation
Serial communication error between controller and drivers
Reset
Automatic
Reset mode
As soon as serial communication is restored
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Involved circuit
Stop
The other devices
They follow their control
4.3.3 Humidifier alarms
The controller manages different alarms which are dependant on the connected humidifier.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
PAL73
1
s
CPY humidifier - General alarm - Alarm delay upon activation
PAL74
5
-
CPY humidifier - General alarm - Max. number of alarms per hour
PAL75
1
s
CPY humidifier - General warning message - Alarm delay upon activation
PAL76
5
-
CPY humidifier - General warning message - Max. number of alarms per hour
CPY humidifier – General alarm
Alarm code
AL162
Reason for activation
General alarm in CPY board after the delay set in parameter “PAL73”
Reset
As soon as the alarm in the CPY board is cleared.
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL74”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Humidifier
According to parameters set in CPY board
The other devices
They follow their control
CPY humidifier – General warning message
Alarm code
AL163
Reason for activation
General alarm in CPY board after the delay set in parameter “PAL75”
Reset
As soon as the alarm in the CPY board is cleared.
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL76”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Humidifier
According to parameters set in CPY board
The other devices
They follow their control
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...