4.2.8 Power supply alarm
The controller is designed to control either the phase sequence or min. and max. power voltage monitoring through a digital
input. The type of monitoring process is selected at the factory and it is set in parameter “CF17” (0 = phase sequence or
min./max. voltage; 1 = min./max. Voltage or blackout).
Phase sequence or min./max. voltage alarm
Alarm code
AL55
Reason for activation
When the corresponding digital input is open.
Reset
Cut off and restore power to the controller.
Reset mode
Always automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
Operation is inhibited.
Min./Max. voltage alarm - Blackout
Alarm code
AL201
Reason for activation
When the corresponding digital input is open.
Reset
Upon closing of the digital input, after the delay set in parameter “CO30”
Reset mode
Always automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
All outputs are disabled.
Fast Restart alarms
Alarm code
AL191 Max. number of fast starts in 1 hour achieved
Reason for activation
As soon as the number of start-ups set in parameter “PAL33” is achieved.
Reset
One hour after alarm “AL201” causing the activation has tripped.
Reset mode
Automatic only
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
All outputs are disabled.
Alarm code
AL192 Max. number of fast starts in twenty-four hours achieved
Reason for activation
As soon as the number of start-ups set in parameter “PAL33” is achieved.
Reset
One hour after alarm “AL201” causing the activation has tripped.
Reset mode
Automatic only
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
All outputs are disabled.
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...