ESIE21-02 – 2021.03
4.6.2 Humidity probes
Return air humidity
Alarm code
AL78
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
humidity control
Humidity control is stopped.
The other devices
They follow their control
External air humidity
Alarm code
AL79
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
They follow their own setup parameters: if the probe experiences a fault, all the tests requi
-
red to start the functions connected to the external humidity value are bypassed.
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...