115
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.6.3 Pressure probes
Condensing pressure
Alarm code
AL94 for circuit 1; AL95 for circuit 2
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
Evaporating pressure
Alarm code
AL98 for circuit 1; AL99 for circuit 2
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Compressors
Only the compressors of the circuit involved are switched off
The other devices
They follow their control
Delivery air differential pressure
Alarm code
AL106
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Unit fan
If the unit has been running for the past thirty minutes, the fan keeps the speed value calcu
-
lated as the average of the measured values, otherwise the unit stops.
The other devices
They follow their own setup parameters if the fan stays operational, otherwise they stop.
Differential air pressure in return line
Alarm code
AL72
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Unit fan
If the unit has been running for the past thirty minutes, the fan keeps the speed value calcu
-
lated as the average of the measured values, otherwise the unit stops.
The other devices
They follow their own setup parameters if the fan stays operational, otherwise they stop.
4 Alarms
Summary of Contents for UATYA-B
Page 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Page 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Page 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...