![background image](http://html1.mh-extra.com/html/daikin/super-multi-nx-b-series/super-multi-nx-b-series_service-manual_2459105052.webp)
Si12-308
Specifications
Specifications
41
1.3
Indoor Units - Heat Pump
Wall Mounted Type
50Hz 220V
Model
FTXE25BVMC
FTXE35BVMC
Cooling
Heating
Cooling
Heating
Rated Capacity
2.5kW Class
3.5kW Class
Front Panel Color
White
White
Air Flow Rates
m³/min
(cfm)
H
7.8 (275)
8.1 (286)
7.7 (272)
8.1 (286)
M
6.4 (226)
6.6 (233)
6.3 (222)
6.6 (233)
L
5.0 (177)
5.1 (180)
4.9 (173)
5.1 (180)
SL
4.3 (152)
4.3 (152)
4.4 (155)
4.4 (155)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
18
18
Speed
Steps
5 Steps, Silent and Auto
5 Steps, Silent and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.17
0.17
0.17
0.17
Power Consumption (Rated)
W
37
37
37
37
Power Factor
%
98.9
98.9
98.9
98.9
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
273×784×195
273×784×195
Packaged Dimensions (W×D×H)
mm
834×325×258
834×325×258
Weight
kg
7.5
7.5
Gross Weight
kg
11
11
Operation
Sound
H/M/L/SL
dBA
37/34/30/27
37/34/30/27
38/37/32/29
38/35/31/28
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
9.5
φ
12.7
Drain
mm
φ
18.0
φ
18.0
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Model
FTXD50BVMC
FTXD60BVMC
Cooling
Heating
Cooling
Heating
Rated Capacity
5.0kW Class
6.0kW Class
Front Panel Color
White
White
Air Flow Rates
m³/min
(cfm)
H
12.3 (434)
12.5 (441)
17.5 (617)
18.7 (660)
M
10.4 (367)
11.0 (388)
14.6 (517)
16.1 (567)
L
8.7 (307)
9.6 (339)
12.2 (431)
13.6 (481)
SL
7.7 (272)
8.2 (289)
10.8 (383)
11.8 (418)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
40
43
Speed
Steps
5 Steps, Silent and Auto
5 Steps, Silent and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.21
0.23
0.21
0.21
Power Consumption (Rated)
W
45
50
45
45
Power Factor
%
97.4
98.8
97.4
97.4
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
290×795×238
290×1,050×238
Packaged Dimensions (W×D×H)
mm
840×338×280
1,147×366×337
Weight
kg
9
12
Gross Weight
kg
13
17
Operation
Sound
H/M/L/SL
dBA
44/39/35/32
42/37/33/30
45/41/36/33
44/40/35/32
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
15.9
Drain
mm
φ
18.0
φ
18.0
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...