Si12-308
Troubleshooting
Service Diagnosis
201
5.22
Output Over Current Detection
Remote
Controller
Display
L5
Outdoor Unit LED
Display
A
5
1
1
2
1
3
4
4
1
Method of
Malfunction
Detection
An output over-current is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output over-current input is fed from the output over-current detection circuit to the
microcomputer.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Over-current due to defective power transistor
Over-current due to wrong internal wiring
Over-current due to abnormal supply voltage
Over-current due to defective PCB
Error detection due to defective PCB
Over-current due to closed stop valve
Over-current due to compressor failure
Over-current due to poor installation condition
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...