Outdoor Unit (52 / 58 / 68 / 75 Class)
Si12-308
244
Removal Procedure
3
Pull out the terminal
board to open.
Glass tube fuse and varistor
cannot be replaced
individually because lead-
free soldering is provided.
2. Remove each wire
harness
When reconnecting, make
sure to match the wire to the
correct connector.
1
Disconnect 4
connectors of the
electronic expansion
valve lead wires.
2
Remove the four way
valve connector S80.
3
Disconnect the
thermistor connector
and the overload relay
connector.
S40
:
Overload relay
S90
:
Thermistor
(Outdoor air, heat
exchanger, discharge pipe)
S92
:
Gas pipe thermistor
S93
:
Liquid pipe thermistor
Step
Procedure
Points
Connector
Electronic
expansion
valve No.
Harness
length
S20
(White)
EVA
630
S21
(Red)
EVB
730
S22
(Blue)
EVC
825
S23
(Yellow)
EVD
940