Si12-308
Specifications
Specifications
53
Floor / Ceiling Suspended Dual Type
230V, 50Hz
Model
FLXS25BVMB
FLXS35BVMB
Cooling
Heating
Cooling
Heating
Rated Capacity
2.5kW Class
3.5kW Class
Front Panel Color
Almond White
Almond White
Air Flow Rates
m³/min
(cfm)
H
7.6 (268)
9.2 (325)
8.6 (304)
9.8 (346)
M
6.8 (240)
8.3 (293)
7.6 (268)
8.9 (314)
L
6.0 (212)
7.4 (261)
6.6 (233)
8.0 (282)
SL
5.2 (184)
6.6 (233)
5.6 (198)
7.2 (254)
Fan
Type
Sirocco Fan
Sirocco Fan
Motor Output
W
34
34
Speed
Steps
5 Steps, Silent and Auto
5 Steps, Silent and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removal-Washable-Mildew Proof
Removal-Washable-Mildew Proof
Running Current (Rated)
A
0.32
0.34
0.36
0.36
Power Consumption (Rated)
W
70
74
78
78
Power Factor
%
95.1
94.6
94.2
94.2
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
490×1,050×200
490×1,050×200
Packaged Dimension
mm
1,100×566×280
1,100×566×280
Weight
kg
16
16
Gross Weight
kg
22
22
Operation
Sound
H/M/L/SL
dBA
37/34/31/28
37/34/31/29
38/35/32/29
39/36/33/30
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
9.5
φ
9.5
Drain
mm
φ
18.0
φ
18.0
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Model
FLXS50BVMB
FLXS60BVMB
Cooling
Heating
Cooling
Heating
Rated Capacity
5.0kW Class
5.7kW Class
Front Panel Color
Almond White
Almond White
Air Flow Rates
m³/min
(cfm)
H
11.4 (402)
12.1 (427)
12.0 (424)
12.8 (452)
M
10.0 (353)
9.8 (346)
10.7 (378)
10.6 (374)
L
8.5 (300)
7.5 (265)
9.3 (328)
8.4 (297)
SL
7.5 (265)
6.8 (240)
8.3 (293)
7.5 (265)
Fan
Type
Sirocco Fan
Sirocco Fan
Motor Output
W
34
34
Speed
Steps
5 Steps, Silent and Auto
5 Steps, Silent and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removal-Washable-Mildew Proof
Removal-Washable-Mildew Proof
Running Current (Rated)
A
0.45
0.45
0.45
0.43
Power Consumption (Rated)
W
96
96
98
96
Power Factor
%
92.8
92.8
94.7
97.1
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
490×1,050×200
490×1,050×200
Packaged Dimension
mm
1,100×566×280
1,100×566×280
Weight
kg
17
17
Gross Weight
kg
24
24
Operation
Sound
H/M/L/SL
dBA
47/43/39/36
46/41/35/33
48/45/41/39
47/42/37/34
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
12.7
Drain
mm
φ
18.0
φ
18.0
Summary of Contents for Super Multi NX B series
Page 7: ...Si12 308 vi Table of Contents ...
Page 29: ...List of Functions Si12 308 18 List of Functions ...
Page 71: ...Specifications Si12 308 60 Specifications ...
Page 175: ...Instruction Si12 308 164 System Configuration ...
Page 227: ...Check Si12 308 216 Service Diagnosis ...
Page 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Page 299: ...Si12 308 iv Index ...